Functional Features
The KS-9000-1 gas alarm controller host is embedded with microprocessor, equipped with rich software functions to complete transmitter signal sampling, real-time data calculation, system fault detection, power management, alarm display, alarm peripheral driving and other functions;
It has 1 analog channel, and can manage 1 output signal as (4-20) mA transmitter;
It has 2-channel relay nodes, which can be connected to control fans, solenoid valves, etc.
It is possible to manage transmitters that detect different gas types, different ranges, and different data units;
Intelligent system: Convenient online zero-point correction;
It is simple to install. Install 2 M4 expansion bolts according to the installation size on the wall, and install it by hanging the controller;
Technical Specifications
Installation method: wall-mounted
Applicable transmitter model: KB-501 series detector
Response time: ≤10s
Indication method: 4-digit digital tube display, LED indicates alarm or fault status, sound prompts alarm and fault
Alarm output: Passive contact Capacity 5A/AC220V (DC24V)
Working method: continuous work
Working ambient temperature: -20℃~45℃
Working environment humidity: ≤95%RH
Main power supply: AC220V±15%, 50Hz±1%
Power: ≤5W
Transmitter power supply voltage: DC24V±25%
External dimensions: 250mm×190mm×99mm (length×width×thickness)
Cable requirements: analog quantity (4-20mA) ≥RVVP 3×1 mm2